iec dien cong nghiep
contents
A
A. contents
B. general - installed power
1. methodology
2. rules and statutory regulations
2.1 definition of voltage ranges
table B1
standard voltages between 100 V and 1000 V (IEC 38-1983)
table B2
standard voltages above 1 kV and not exceeding 35 kV (IEC 38-1983)
B1
B3
B3
B3
B3
B4
B4
B5
B6
B6
B6
B7
B8
B8
B9
B10
B10
B10
B11
A1
2.2 regulations
2.3 standards
2.4 quality and safety of an electrical installation
2.5 initial testing of an installation
2.6 periodic check-testing of an installation
table B3
frequency of check-tests commonly recommended for an electrical installation
2.7 conformity (with standards and specifications) of equipment
used in the installation
3. motor, heating and lighting loads
3.1 induction motors
table B4
power and current values for typical induction motors
3.2 direct-current motors
table B6
progressive starters with voltage ramp
table B7
progressive starters with current limitation
3.3 resistive-type heating appliances and incandescent lamps
(conventional or halogen)
table B8
current demands of resistive heating and incandescent lighting (conventional or halogen)
appliancesB11
3.4 fluorescent lamps and related equipment
table B10
current demands and power consumption of commonly-dimensioned fluorescent
lighting tubes (at 220 V/240 V - 50 Hz)
table B11
current demands and power consumption of compact fluorescent lamps
(at 220 V/240 V - 50 Hz)
B11
B12
B12
B13
B13
B14
B14
B15
B15
B16
B16
B17
B17
B17
B17
3.5 discharge lamps
table B12
current demands of discharge lamps
4. power loading of an installation
4.1 installed power (kW)
4.2 installed apparent power (kVA)
table B13
estimation of installed apparent power
4.3 estimation of actual maximum kVA demand
table B14
simultaneity factors in an apartment block
table B16
factor of simultaneity for distribution boards (IEC 439)
table B17
factor of simultaneity according to circuit function
4.4 example of application of factors ku and ks
table B18
an example in estimating the maximum predicted loading of an installation
(the factor values used are for demonstration purposes only)
contents - A1
contents (continued)
A
B. general - installed power (continued)
4. power loading of an installation (continued)
4.5 diversity factor
4.6 choice of transformer rating
table B19
IEC-standardized kVA ratings of HV/LV 3-phase distribution transformers
and corresponding nominal full-load current values
B18
B18
B18
B19
4.7 choice of power-supply sources
C. HV/LV distribution substations
1. supply of power at high voltage
1.1 power-supply characteristics of high voltage distribution networks
table C1
relating nominal system voltages with corresponding rated system voltages
(r.m.s. values)
table C2
switchgear rated insulation levels
table C3A
transformers rated insulation levels in series I (based on current practice other than
in the United States of America and some other countries)
table C3B
transformers rated insulation levels in series II (based on current practice in the United
States of America and some other countries)
table C4
standard short-circuit current-breaking ratings extracted from table X IEC 56
C1
C1
C2
C3
C3
C4
C4
C11
C13
C15
C15
C17
C17
C22
C25
C26
C27
C31
C31
C34
C34
C36
C37
C38
C38
C41
C42
C44
C44
C46
C48
C49
C49
C49
C52
1.2 different HV service connections
1.3 some operational aspects of HV distribution networks
2. consumers HV substations
2.1 procedures for the establishment of a new substation
3. substation protection schemes
3.1 protection against electric shocks and overvoltages
3.2 electrical protection
table C18
power limits of transformers with a maximum primary current not exceeding 45 A
table C19
rated current (A) of HV fuses for transformer protection according to IEC 282-1
table C20
3-phase short-circuit currents of typical distribution transformers
3.3 protection against thermal effects
3.4 interlocks and conditioned manœuvres
4. the consumer substation with LV metering
4.1 general
4.2 choice of panels
table C27
standard short-circuit MVA and current ratings at different levels of nominal voltage
4.3 choice of HV switchgear panel for a transformer circuit
4.4 choice of HV/LV transformer
table C31
categories of dielectric fluids
table C32
safety measures recommended in electrical installations using dielectric liquids
of classes 01, K1, K2 or K3
5. a consumer substation with HV metering
5.1 general
5.2 choice of panels
5.3 parallel operation of transformers
6. constitution of HV/LV distribution substations
6.1 different types of substation
6.2 indoor substations equipped with metal-enclosed switchgear
6.3 outdoor substations
A2 - contents
A
7. appendix 1 : example in coordination of the
characteristics of an HV switch-fuse combination
protecting an HV/LV transformer
7.1 transfert current and take-over current
7.2 types of faults involved in the transfer region
App C1-1
App C1-2
App C1-3
8. appendix 2 : ground-surface potential gradients
due to earth-fault currents
9. appendix 3 : vector diagram of ferro-resonance
at 50Hz (or 60 Hz)
App C2-1
App C3-1
D. low-voltage service connections
1. low-voltage public distribution networks
1.1 low-voltage consumers
table D1
survey of electricity supplies in various countries around the world.
table D2
D1
D1
D1
D6
D7
D10
D13
D14
1.2 LV distribution networks
1.3 the consumer-service connection
1.4 quality of supply voltage
2. tariffs and metering
E. power factor improvement and harmonic filtering
1. power factor improvement
1.1 the nature of reactive energy
1.2 plant and appliances requiring reactive current
1.3 the power factor
1.4 tan ϕ
1.5 practical measurement of power factor
1.6 practical values of power factor
table E5
example in the calculation of active and reactive power
table E7
values of cos ϕand tan ϕfor commonly-used plant and equipment
E1
E1
E2
E2
E3
E4
E4
E4
E4
E5
E5
E5
E5
E6
E6
E7
E8
E9
E9
E9
E10
2. why improve the power factor?
2.1 reduction in the cost of electricity
2.2 technical/economic optimization
table E8
multiplying factor for cable size as a function of cos ϕ
3. how to improve the power factor
3.1 theoretical principles
3.2 by using what equipment?
3.3 the choice between a fixed or automatically-regulated bank
of capacitors
4. where to install correction capacitors
4.1 global compensation
4.2 compensation by sector
4.3 individual compensation
contents - A3
contents (continued)
A
E. power factor improvement and harmonic filtering (continued)
5. how to decide the optimum level of compensation
5.1 general method
5.2 simplified method
table E17
kvar to be installed per kW of load, to improve the power factor of an installation
E11
E11
E11
E12
E13
E13
E14
E14
E14
E15
E16
5.3 method based on the avoidance of tariff penalties
5.4 method based on reduction of declared maximum apparent
power (kVA)
6. compensation at the terminals of a transformer
6.1 compensation to increase the available active power output
table E20
active-power capability of fully-loaded transformers, when supplying loads at different
values of power factor
6.2 compensation of reactive energy absorbed by the transformer
table E24
reactive power consumption of distribution transformers with 20 kV primary windings
7. compensation at the terminals of an induction motor E17
7.1 connection of a capacitor bank and protection settings
table E26
reduction factor for overcurrent protection after compensation
E17
E17
E18
E19
7.2 how self-excitation of an induction motor can be avoided
table E28
maximum kvar of P.F. correction applicable to motor terminals without risk
of self-excitation
8. example of an installation before and after
power-factor correction
9. the effect of harmonics on the rating of a capacitor
bank
9.1 problems arising from power-system harmonics
9.2 possible solutions
9.3 choosing the optimum solution
table E30
choice of solutions for limiting harmonics associated with a LV capacitor bank
E20
E21
E21
E21
E22
E22
E23
E24
E24
E25
9.4 possible effects of power-factor-correction capacitors
on the power-supply system
10. implementation of capacitor banks
10.1 capacitor elements
10.2 choice of protection, control devices, and connecting cables
11. appendix 1 : elementary harmonic filters
12. appendix 2 : harmonic suppression reactor
for a single (power factor correction)
capacitor bank
App E3-1
App E4-1
F. distribution within a low-voltage installation
1. general
1.1 the principal schemes of LV distribution
1.2 the main LV distribution board
1.3 transition from IT to TN
F1
F1
F4
F4
A4 - contents
A
2. essential services standby supplies
2.1 continuity of electric-power supply
2.2 quality of electric-power supply
table F10
assumed levels of transient overvoltage possible at different points of a typical
installation
table F12
typical levels of impulse withstand voltage of industrial circuit breakers labelled
Uimp = 8 kV
table F18
compatibility levels for installation materials
F5
F5
F6
F8
F8
F13
3. safety and emergency-services installations,
and standby power supplies
3.1 safety installations
3.2 standby reserve-power supplies
3.3 choice and characteristics of reserve-power supplies
table F21
table showing the choice of reserve-power supply types according to application
requirements and acceptable supply-interruption times
F15
F15
F15
F16
F16
F17
F17
F18
F19
F19
F20
F21
F23
F29
F30
F31
F32
F33
F33
F36
F36
F37
F38
F38
F39
F39
F41
F41
F41
F43
F44
F45
F46
3.4 choice and characteristics of different sources
table F22
table of characteristics of different sources
3.5 local generating sets
4. earthing schemes
4.1 earthing connections
table F25
list of exposed-conductive-parts and extraneous-conductive-parts
4.2 definition of standardized earthing schemes
4.3 earthing schemes characteristics
4.4.1 choice criteria
4.4.2 comparison for each criterion
4.5 choice of earthing method - implementation
4.6 installation and measurements of earth electrodes
table F47
resistivity (Ω-m) for different kinds of terrain
table F48
mean values of resistivity (Ω-m) for an approximate estimation of an earth-electrode
resistance with respect to zero-potential earth
5. distribution boards
5.1 types of distribution board
5.2 the technologies of functional distribution boards
5.3 standards
5.4 centralized control
6. distributors
6.1 description and choice
6.2 conduits, conductors and cables
table F60
selection of wiring systems
table F61
erection of wiring systems
table F62
some examples of installation methods
table F63
designation code for conduits according to the most recent IEC publications
table F64
designation of conductors and cables according to CENELEC code for harmonized
cables
table F66
commonly used conductors and cables
contents - A5
contents (continued)
A
F. distribution within a low-voltage installation (continued)
7. external influences
7.1 classification
table F67
concise list of important external influences (taken from Appendix A of IEC 364-3)
F47
F47
F48
F49
7.2 protection by enclosures: IP code
G. protection against electric shocks
1. general
1.1 electric shock
1.2 direct and indirect contact
G1
G1
G1
G2
G2
G3
G4
G4
G4
G4
G5
G6
G6
G7
G8
G9
G10
G13
G13
2. protection against direct contact
2.1 measures of protection against direct contact
2.2 additional measure of protection against direct contact
3. protection against indirect contact
3.1 measure of protection by automatic disconnection of the supply
table G8
maximum safe duration of the assumed values of touch voltage in conditions where
UL = 50 V
table G9
maximum safe duration of the assumed values of touch voltage in conditions where
UL = 25 V
3.2 automatic disconnection for a TT-earthed installation
table G11
maximum operating times of RCCBs (IEC 1008)
3.3 automatic disconnection for a TN-earthed installation
table G13
maximum disconnection times specified for TN earthing schemes (IEC 364-4-41)
3.4 automatic disconnection on a second earth fault in an IT-earthed
system
table G18
maximum disconnection times specified for an IT-earthed installation (IEC 364-4-41)
3.5 measures of protection against direct or indirect contact
without circuit disconnection
4. implementation of the TT system
4.1 protective measures
table G26
the upper limit of resistance for an installation earthing electrode which must not be
exceeded, for given sensitivity levels of RCDs at UL voltage limits of 50 V and 25 V
G13
G14
G15
G18
G18
G18
G20
G20
G20
G21
G21
G22
G22
G23
4.2 types of RCD
4.3 coordination of differential protective devices
5. implementation of the TN system
5.1 preliminary conditions
5.2 protection against indirect contact
table G42
correction factor to apply to the lengths given in tables G43 to G46 for TN systems
table G43
maximum circuit lengths for different sizes of conductor and
instantaneous-tripping-current settings for general-purpose circuit breakers
table G44
maximum circuit lengths for different sizes of conductor and rated currents for type B
circuit breakers
table G45
maximum circuit lengths for different conductor sizes and for rated currents of circuit
breakers of type C
table G46
maximum circuit lengths for different conductor sizes and for rated currents of circuit
breakers of type D or MA Merlin Gerin
5.3 high-sensitivity RCDs
5.4 protection in high fire-risk locations
5.5 when the fault-current-loop impedance is particularly high
A6 - contents
A
6. implementation of the IT system
6.1 preliminary conditions
table G53
essential functions in IT schemes
G24
G24
G24
G25
G28
G29
G29
G30
G31
G31
G31
G32
G33
G34
G34
6.2 protection against indirect contact
table G59
correction factors, for IT-earthed systems, to apply to the circuit lengths given
in tables G43 to G46
6.3 high-sensitivity RCDs
6.4 in areas of high fire-risk
6.5 when the fault-current-loop impedance is particularly high
7. residual current differential devices (RCDs)
7.1 description
7.2 application of RCDs
table G70
electromagnetic compatibility withstand-level tests for RCDs
table G72
means of reducing the ratio I∆n/lph (max.)
7.3 choice of characteristics of a residual-current circuit breaker
(RCCB - IEC 1008)
table G74
typical manufacturers coordination table for RCCBs, circuit breakers, and fuses
H. the protection of circuits and the switchgear
H1. the protection of circuits
1. general
1.1 methodology and definitions
table H1-1
logigram for the selection of cable size and protective-device rating for a given circuit
H1-1
H1-1
H1-1
H1-3
H1-4
H1-5
H1-5
H1-5
H1-6
H1-8
H1-9
1.2 overcurrent protection principles
1.3 practical values for a protection scheme
1.4 location of protective devices
table H1-7
general rules and exceptions concerning the location of protective devices
1.5 cables in parallel
1.6 worked example of cable calculations
table H1-9
calculations carried out with ECODIAL software (Merlin Gerin)
table H1-10
example of short-circuit current evaluation
2. practical method for determining the smallest
allowable cross-sectional-area of circuit conductors
2.1 general
table H1-11
logigram for the determination of minimum conductor size for a circuit
H1-10
H1-10
H1-10
H1-10
H1-10
H1-11
H1-11
H1-12
H1-13
2.2 determination of conductor size for unburied circuits
table H1-12
code-letter reference, depending on type of conductor and method of installation
table H1-13
factor K1 according to method of circuit installation (for further examples refer
to IEC 364-5-52 table 52H)
table H1-14
correction factor K2 for a group of conductors in a single layer
table H1-15
correction factor K3 for ambient temperature other than 30
table H1-17
case of an unburied circuit: determination of the minimum cable size (c.s.a.), derived
from the code letter; conductor material; insulation material and the fictitious current I'z
contents - A7
contents (continued)
A
H. the protection of circuits and the switchgear (continued)
H1. the protection of circuits (continued)
2. practical method for determining the smallest
allowable cross-sectional-area of circuit conductors (continued)
2.3 determination of conductor size for buried circuits
table H1-19
correction factor K4 related to the method of installation
table H1-20
correction factor K5 for the grouping of several circuits in one layer
table H1-21
correction factor K6 for the nature of the soil
table H1-22
correction factor K7 for soil temperatures different than 20
table H1-24
case of a buried circuit: minimum c.s.a. in terms of type of conductor; type of insulation;
and value of fictitious current I'z (I'z = Iz)
K
H1-14
H1-14
H1-14
H1-15
H1-15
H1-15
3. determination of voltage drop
3.1 maximum voltage-drop limit
table H1-26
maximum voltage-drop limits
H1-17
H1-17
H1-17
H1-18
H1-18
H1-18
H1-20
H1-20
H1-20
H1-20
H1-21
H1-21
H1-22
H1-23
H1-23
H1-23
3.2 calculation of voltage drops in steady load conditions
table H1-28
voltage-drop formulae
table H1-29
phase-to-phase voltage drop ∆for a circuit, in volts per ampere per km
4. short-circuit current calculations
4.1 short-circuit current at the secondary terminals of a HV/LV
distribution transformer
table H1-32
typical values of Usc for different kVA ratings of transformers with HV windings i 20 kV
table H1-33
Isc at the LV terminals of 3-phase HV/LV transformers supplied from a HV system
with a 3-phase fault level of 500 MVA, or 250 MVA
4.2 3-phase short-circuit current (Isc) at any point within
a LV installation
table H1-36
the impedance of the HV network referred to the LV side of the HV/LV transformer
table H1-37
resistance, reactance and impedance values for typical distribution transformers
with HV windings i 20 kV
table H1-38
recapitulation table of impedances for different parts of a power-supply system
table H1-39
example of short-circuit current calculations for a LV installation supplied at 400 V
(nominal) from a 1,000 kVA HV/LV transformer
4.3 Isc at the receiving end of a feeder in terms of the Isc
at its sending end
table H1-40
Isc at a point downstream, in terms of a known upstream fault-current value
and the length and c.s.a. of the intervening conductors, in a 230/400 V 3-phase system
H1-24
H1-25
H1-26
H1-26
4.4 short-circuit current supplied by an alternator or an inverter
5. particular cases of short-circuit current
5.1 calculation of minimum levels of short-circuit current
table H1-49
maximum circuit lengths in metres for copper conductors (for aluminium, the lengths
must be multiplied by 0.62)
table H1-50
maximum length of copper-conductored circuits in metres protected by B-type
circuit breakers
table H1-51
maximum length of copper-conductored circuits in metres protected by C-type
circuit breakers
table H1-52
maximum length of copper-conductored circuits in metres protected by D-type
circuit breakers
table H1-53
correction factors to apply to lengths obtained from tables H1-49 to H1-52
A8 - contents
H1-28
H1-29
H1-29
H1-29
H1-30
A
5.2 verification of the withstand capabilities of cables
under short-circuit conditions
table H1-54
value of the constant k2
table H1-55
maximum allowable thermal stress for cables (expressed in amperes2 x seconds x 106)
H1-31
H1-31
H1-31
H1-32
H1-32
H1-33
H1-33
6. protective earthing conductors (PE)
6.1 connection and choice
table H1-59
choice of protective conductors (PE)
6.2 conductor dimensioning
table H1-60
minimum c.s.a.'s for PE conductors and earthing conductors
(to the installation earth electrode)
table H1-61
k factor values for LV PE conductors, commonly used in national standards
and complying with IEC 724
H1-34
H1-34
H1-35
6.3 protective conductor between the HV/LV transformer
and the main general distribution board (MGDB)
table H1-63
c.s.a. of PE conductor between the HV/LV transformer and the MGDB, in terms of transformer
ratings and fault-clearance times used in FranceH1-35
6.4 equipotential conductor
7. the neutral conductor
7.1 dimensioning the neutral conductor
7.2 protection of the neutral conductor
table H1-65
table of protection schemes for neutral conductors in different earthing systems
H1-35
H1-36
H1-36
H1-36
H1-37
H2. the switchgear
1. the basic functions of LV switchgear
table H2-1
basic functions of LV switchgear
H2-1
H2-1
H2-1
H2-1
H2-2
H2-2
H2-4
H2-4
H2-5
H2-5
H2-7
H2-9
H2-11
H2-11
H2-11
H2-11
1.1 electrical protection
1.2 isolation
table H2-2
peak value of impulse voltage according to normal service voltage of test specimen
1.3 switchgear control
2. the switchgear and fusegear
2.1 elementary switching devices
table H2-7
utilization categories of LV a.c. switches according to IEC 947-3
table H2-8
factor "n" used for peak-to-rms value (IEC 947-part 1)
table H2-13
zones of fusing and non-fusing for LV types gG and gM class fuses
(IEC 269-1 and 269-2-1)
2.2 combined switchgear elements
3. choice of switchgear
3.1 tabulated functional capabilities
table H2-19
functions fulfilled by different items of switchgear
3.2 switchgear selection
contents - A9
contents (continued)
A
H2. the switchgear (continued)
4. circuit breakers
table H2-20
functions performed by a circuit breaker/disconnector
H2-12
H2-12
H2-12
H2-15
H2-16
H2-17
4.1 standards and descriptions
4.2 fundamental characteristics of a circuit breaker
table H2-28
tripping-current ranges of overload and short-circuit protective devices
for LV circuit breakers
table H2-31
Icu related to power factor (cos ϕof fault-current circuit (IEC 947-2)
4.3 other characteristics of a circuit breaker
H2-18
table H2-34
relation between rated breaking capacity Icu and rated making capacity Icm at different
power-factor values of short-circuit current, as standardized in IEC 947-2H2-19
4.4 selection of a circuit breaker
table H2-38
examples of tables for the determination of derating/uprating factors to apply to CBs
with uncompensated thermal tripping units, according to temperature
table H2-40
different tripping units, instantaneous or short-time delayed
table H2-43
maximum values of short-circuit current to be interrupted by main and principal
circuit breakers (CBM and CBP respectively), for several transformers in parallel
H2-20
H2-21
H2-23
H2-25
H2-27
H2-28
H2-29
H2-32
4.5 coordination between circuit breakers
table H2-45
example of cascading possibilities on a 230/400 V or 240/415 V 3-phase installation
table H2-49
summary of methods and components used in order to achieve discriminative tripping
4.6 discrimination HV/LV in a consumer's substation
J. particular supply sources and loads
1. protection of circuits supplied by an alternator
1.1 an alternator on short-circuit
1.2 protection of essential services circuits supplied in emergencies
from an alternator
1.3 choice of tripping units
1.4 methods of approximate calculation
table J1-7
procedure for the calculation of 3-phase short-circuit current
table J1-8
procedure for the calculation of 1-phase to neutral short-circuit current
J1
J1
J4
J5
J6
J6
J7
J9
1.5 the protection of standby and mobile a.c. generating sets
2. inverters and UPS
(Uninterruptible Power Supply units)
2.1 what is an inverter?
2.2 types of UPS system
J10
J10
J10
table J2-4
examples of different possibilities and applications of inverters, in decontamination of supplies
and in UPS schemesJ11
J11
J12
J14
J15
J17
2.3 standards
2.4 choice of a UPS system
2.5 UPS systems and their environment
2.6 putting into service and technology of UPS systems
2.7 earthing schemes
A10 - contents
A
2.8 choice of main-supply and circuit cables, and cables for the battery
connection
table J2-21
voltage drop in % of 324 V d.c. for a copper-cored cable
table J2-22
currents and c.s.a. of copper-cored cables feeding the rectifier, and supplying the load
for UPS system Maxipac (cable lengths < 100 m)
table J2-23
currents and c.s.a. of copper-cored cables feeding the rectifier, and supplying the load
for UPS system EPS 2000 (cable lengths < 100 m). Battery cable data are also included
table J2-24
input, output and battery currents for UPS system EPS 5000 (Merlin Gerin)
J20
J21
J21
J21
J22
J23
J24
J25
J25
J25
J26
J26
J26
J26
J27
J27
J28
J29
J29
J30
J30
J31
J31
2.9 choice of protection schemes
2.10 complementary equipments
3. protection of LV/LV transformers
3.1 transformer-energizing in-rush current
3.2 protection for the supply circuit of a LV/LV transformer
3.3 typical electrical characteristics of LV/LV 50 Hz transformers
table J3-5
typical electrical characteristics of LV/LV 50 Hz transformers
3.4 protection of transformers with characteristics as tabled in J3-5
above, using Merlin Gerin circuit breakers
table J3-6
protection of 3-phase LV/LV transformers with 400 V primary windings
table J3-7
protection of 3-phase LV/LV transformers with 230 V primary windings
table J3-8
protection of 1-phase LV/LV transformers with 400 V primary windings
table J3-9
protection of 1-phase LV/LV transformers with 230 V primary windings
4. lighting circuits
4.1 service continuity
4.2 lamps and accessories (luminaires)
table J4-1
analysis of disturbances in fluorescent-lighting circuits
4.3 the circuit and its protection
4.4 determination of the rated current of the circuit breaker
table J4-2
protective circuit breaker ratings for incandescent lamps and resistive-type heating
circuits
table J4-3
maximum limit of rated current per outgoing lighting circuit, for high-pressure discharge
lamps
table J4-4
current ratings of circuit breakers related to the number of fluorescent luminaires to be
protected
J31
J32
J32
J33
J33
J34
J35
J36
J36
J37
J38
J38
J39
J41
4.5 choice of control-switching devices
table J4-5
types of remote control
4.6 protection of ELV lighting circuits
4.7 supply sources for emergency lighting
5. asynchronous motors
5.1 protective and control functions required
table J5-2
commonly-used types of LV motor-supply circuits
5.2 standards
5.3 basic protection schemes: circuit breaker / contactor / thermal relay
table J5-4
utilization categories for contactors (IEC 947-4)
5.4 preventive or limitative protection
contents - A11
contents (continued)
A
J. particular supply sources and loads (continued)
5. asynchronous motors (continued)
5.5 maximum rating of motors installed for consumers supplied at LV
table J5-12
maximum permitted values of starting current for direct-on-line LV motors (230/400 V)
table J5-13
maximum permitted power ratings for LV direct-on-line-starting motors
J43
J43
J43
J43
J44
J44
J45
J45
J45
J46
J46
J47
5.6 reactive-energy compensation (power-factor correction)
6. protection of direct-current installations
6.1 short-circuit currents
6.2 characteristics of faults due to insulation failure, and of protective
switchgear
table J6-4
characteristics of protective switchgear according to type of d.c. system earthing
6.3 choice of protective device
table J6-5
choice of d.c. circuit breakers manufactured by Merlin Gerin
6.4 examples
6.5 protection of persons
7. Appendix : Short-circuit characteristics
of an alternator
App J1-1
L. domestic and similar premises and special locations
1. domestic and similar premises
1.1 general
1.2 distribution-board components
1.3 protection of persons
1.4 circuits
table L1-9
recommended minimum number of lighting and power points in domestic premises
table L1-11
c.s.a. of conductors and current rating of the protective devices in domestic
installations (the c.s.a. of aluminium conductors are shown in brackets)
L1
L1
L2
L4
L6
L6
L7
L8
L8
L10
L10
2. bathrooms and showers
2.1 classification of zones
2.2 equipotential bonding
2.3 requirements prescribed for each zone
3. recommendations applicable to special installations
and locations
L11
A12 - contents
Bạn đang đọc truyện trên: Truyen2U.Com